<?xml version="1.0" encoding="UTF-8"?><rss version="2.0"
	xmlns:content="http://purl.org/rss/1.0/modules/content/"
	xmlns:wfw="http://wellformedweb.org/CommentAPI/"
	xmlns:dc="http://purl.org/dc/elements/1.1/"
	xmlns:atom="http://www.w3.org/2005/Atom"
	xmlns:sy="http://purl.org/rss/1.0/modules/syndication/"
	xmlns:slash="http://purl.org/rss/1.0/modules/slash/"
	>

<channel>
	<title>PQA &amp; PMU &#8211; HITEC-INSTRUMENTS</title>
	<atom:link href="https://hitec-instruments.co.uk/product-category/pqa-pmu/feed/" rel="self" type="application/rss+xml" />
	<link>https://hitec-instruments.co.uk</link>
	<description>Equipment Shop WooCommerce WordPress Theme for Machine &#38; Tools</description>
	<lastBuildDate>Fri, 04 Sep 2026 06:29:29 +0000</lastBuildDate>
	<language>en-GB</language>
	<sy:updatePeriod>
	hourly	</sy:updatePeriod>
	<sy:updateFrequency>
	1	</sy:updateFrequency>
	<generator>https://wordpress.org/?v=7.1.5</generator>

<image>
	<url>https://hitec-instruments.co.uk/wp-content/uploads/2025/05/cropped-LOGO-Hitec_последнее-50x50.png</url>
	<title>PQA &amp; PMU &#8211; HITEC-INSTRUMENTS</title>
	<link>https://hitec-instruments.co.uk</link>
	<width>32</width>
	<height>32</height>
</image> 
	<item>
		<title>SATEC PMU PRO – Phasor Measurement Unit</title>
		<link>https://hitec-instruments.co.uk/product/satec-pmu-pro-measurement-unit/</link>
		
		<dc:creator><![CDATA[Online Shopping]]></dc:creator>
		<pubDate>Fri, 13 Feb 2026 09:41:29 +0000</pubDate>
				<guid isPermaLink="false">https://hitec-instruments.co.uk/?post_type=product&#038;p=7386</guid>

					<description><![CDATA[SATEC PMU PRO is a phasor measurement unit used for time-aligned synchrophasor monitoring in wide-area and system-level power systems. It provides consistent phasor data for system visibility, event correlation and analysis of dynamic behaviour across transmission, distribution and critical infrastructure.

&#160;]]></description>
										<content:encoded><![CDATA[<h5>SATEC PMU PRO phasor measurement unit (PMU) designed for synchrophasor-based monitoring (WAMS) and substation data exchange over IEC 61850 and IEEE C37.118.2.</h5>
<p>It is used where time-aligned phasor data is needed for grid visibility, event correlation and wide-area performance monitoring. In practice, the SATEC PMU PRO phasor measurement unit is deployed across transmission, distribution and critical infrastructure where consistent, time-synchronised synchrophasor streams are required.</p>
<p>In operational environments, PMU data is not used in isolation. The SATEC PMU PRO phasor measurement unit becomes critical when multiple measurement points must be time-aligned to reveal system-wide behaviour that is not visible at substation level – such as inter-area oscillations, disturbance propagation and frequency instability under dynamic conditions.</p>
<div style="margin: 24px 0;">
<div style="width: 800px;" class="wp-video"><video class="wp-video-shortcode" id="video-7386-1" width="800" height="451" preload="metadata" controls="controls"><source type="video/mp4" src="https://hitec-instruments.co.uk/wp-content/uploads/2026/02/PMU_REELS_30.12.2024.mp4?_=1" /><a href="https://hitec-instruments.co.uk/wp-content/uploads/2026/02/PMU_REELS_30.12.2024.mp4">https://hitec-instruments.co.uk/wp-content/uploads/2026/02/PMU_REELS_30.12.2024.mp4</a></video></div>
</div>
<h5></h5>
<h5>Key functions</h5>
<ul>
<li>Calculates time-aligned voltage and current phasors, frequency and rate of change of frequency (ROCOF) from sampled waveforms.</li>
<li>Generates synchrophasor data streams with configurable reporting rates for real-time monitoring and post-event analysis.</li>
<li>Maintains sub-microsecond time alignment across distributed measurement points using externally referenced time sources.</li>
<li>Provides deterministic data delivery for wide-area monitoring and disturbance correlation.</li>
<li>Supports simultaneous data streams to multiple clients for parallel monitoring and analysis.</li>
<li>Ensures stable operation under high data rates and continuous streaming conditions.</li>
</ul>
<h5>Measurement inputs and I/O</h5>
<ul>
<li>Synchrophasor measurements compliant with IEEE C37.118.1 for both P-Class and M-Class applications.</li>
<li>High measurement stability under dynamic grid conditions, including frequency deviations and transient events.</li>
<li>Consistent phasor, frequency and ROCOF calculation suitable for wide-area monitoring and system performance analysis.</li>
<li>Designed for continuous operation with deterministic timing and data integrity across long-duration recordings.</li>
</ul>
<h5>Protocols &amp; standards</h5>
<ul>
<li>IEEE C37.118.1 synchrophasor measurement and IEEE C37.118.2 data transfer.</li>
<li><a href="https://iec61850.dvl.iec.ch/?utm_source" target="_blank" rel="noopener">IEC 61850 communications</a>, including IEC 61850-90-5 synchrophasor data exchange.</li>
<li>SCADA integration options: DNP3, Modbus and IEC 60870-5.</li>
</ul>
<h5>Time synchronisation</h5>
<ul>
<li>IEEE 1588 Precision Time Protocol (PTP) and IRIG-B for sub-microsecond alignment of synchrophasor data.</li>
</ul>
<p>In WAMS deployments, PMU data becomes valuable once measurements are taken at more than one location. When sites are properly time-aligned, phase angle and frequency behaviour can be compared directly, oscillations are identified earlier, and disturbances can be correlated across locations without timestamp ambiguity.<br />
SATEC PMU PRO is typically applied in such multi-site monitoring setups.</p>
<h5>Communication &amp; I/O</h5>
<ul>
<li>Dual Ethernet interfaces for parallel data paths and resilient network topologies.</li>
<li>Continuous, high-rate streaming to multiple data consumers in parallel.</li>
<li>Optional plug-in I/O modules for status monitoring and control signalling where required.</li>
</ul>
<h5>Wide-area monitoring and system dynamics</h5>
<ul>
<li>Time-aligned phasor data for wide-area monitoring and grid dynamics analysis.</li>
<li>Correlation of disturbances across geographically distributed measurement points.</li>
<li>Insight into oscillations, frequency behaviour and inter-area interactions.</li>
</ul>
<h5>Typical applications</h5>
<ul>
<li>Wide Area Monitoring Systems (WAMS) for transmission and distribution networks.</li>
<li>Integration with phasor data concentrators (PDCs) for centralised monitoring and analysis.</li>
<li>Grid stability and oscillation monitoring across interconnected networks.</li>
<li>Correlation of events across substations, renewable generation sites and critical infrastructure.</li>
<li>Used for advanced system analysis and post-event investigation.</li>
</ul>
<p>The SATEC PMU PRO phasor measurement unit is typically deployed within wide-area monitoring architectures to support system-level analysis based on time-aligned synchrophasor data.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>SATEC PM175 PRO Power Quality Analyser and Power Meter</title>
		<link>https://hitec-instruments.co.uk/product/satec-pm175-pro-power-quality-analyser-and-power-meter/</link>
		
		<dc:creator><![CDATA[Marketing Hitec]]></dc:creator>
		<pubDate>Sat, 06 Dec 2025 12:14:42 +0000</pubDate>
				<guid isPermaLink="false">https://hitec-instruments.co.uk/?post_type=product&#038;p=7124</guid>

					<description><![CDATA[SATEC PM175 PRO is a modular power quality analyser and power meter combining Class A power quality monitoring with revenue-grade energy metering in a single device. It is designed for LV and MV feeders in substations, industrial plants and commercial installations, providing accurate energy data, disturbance recording and native support for utility communication protocols for seamless integration into SCADA and energy management systems.]]></description>
										<content:encoded><![CDATA[<h4>SATEC PM175 PRO Power Quality Analyser and Power Meter is a combined Class A power quality analyser and revenue-grade energy meter for LV and MV systems.</h4>
<p>For projects that need both accurate billing and detailed power quality information, the SATEC PM175 PRO Power Quality Analyser and Power Meter allows you to standardise on a single platform instead of installing separate meters and PQ analysers.<br data-start="803" data-end="806" />Typical applications include MV and LV switchboards, industrial substations, process lines, generators, UPS and critical loads in data centres and commercial buildings.<br data-start="976" data-end="979" />The SATEC PM175 PRO Power Quality Analyser and Power Meter is equally suited for new projects and retrofit programmes, where panel space, wiring time and integration effort are limited.</p>
<div style="width: 800px;" class="wp-video"><video class="wp-video-shortcode" id="video-7124-2" width="800" height="450" preload="metadata" controls="controls"><source type="video/mp4" src="https://hitec-instruments.co.uk/wp-content/uploads/2025/12/PM17Х.-PRO-SITE-DEVICE-1.mp4?_=2" /><a href="https://hitec-instruments.co.uk/wp-content/uploads/2025/12/PM17Х.-PRO-SITE-DEVICE-1.mp4">https://hitec-instruments.co.uk/wp-content/uploads/2025/12/PM17Х.-PRO-SITE-DEVICE-1.mp4</a></video></div>
<p>For full installation and configuration details, see the official <a href="https://satec-uk.com/files/pm17x-pro/pm17x-pro-installation-and-operation-manual.pdf?srsltid=AfmBOooX_p0h0yLWpTqk8sJzUhleR4AMbBm5dNRxm-MsVWAZFPH5RkUe&amp;utm_source" target="_blank" rel="noopener"><strong data-start="795" data-end="842">PM17X PRO Installation and Operation Manual</strong></a>.</p>
<h4>Key functions</h4>
<ul>
<li data-start="586" data-end="716">Combined power meter and power quality analyser – high-accuracy energy metering and Class A power quality analysis in one device</li>
<li data-start="719" data-end="823">Revenue-grade metering – active energy accuracy Class 0.2S for billing, settlement and cost allocation</li>
<li data-start="826" data-end="947">Class A power quality monitoring – compliant with IEC 61000-4-30 Edition 3 for voltage quality, events and disturbances</li>
<li data-start="950" data-end="1062">Disturbance and fault recording – high-speed transient and RMS recording for detailed fault and event analysis</li>
<li data-start="1065" data-end="1170">Sequence of Events (SOE) – time-stamped event recording for accurate reconstruction of system behaviour</li>
<li data-start="1173" data-end="1318">Advanced communications – native Ethernet and RS-485 with support for standard utility protocols (Modbus, DNP3, IEC 60870-5-101/104, IEC 61850)</li>
<li data-start="1321" data-end="1434">Onboard data storage – internal memory for long-term data logging, power quality reports and compliance records</li>
</ul>
<h4>Measurement inputs and I/O</h4>
<ul>
<li data-start="1470" data-end="1532">Multi-phase voltage and current inputs for LV and MV feeders</li>
<li data-start="1535" data-end="1618">Wide dynamic range current inputs suitable for protection CTs and measurement CTs</li>
<li data-start="1621" data-end="1711">Support for high-accuracy current sensors and retrofittable solutions in existing panels</li>
<li data-start="1714" data-end="1814">Configurable digital inputs and outputs for status indication, alarms and simple control functions</li>
<li data-start="1817" data-end="1904">Plug-in I/O cards to adapt the device to different switchboard and substation layouts</li>
</ul>
<h4 data-start="93" data-end="143">Power quality monitoring and recording</h4>
<ul>
<li data-start="1952" data-end="2060">Continuous Class A monitoring of voltage and frequency, dips, swells, interruptions, flicker and unbalance</li>
<li data-start="2063" data-end="2160">Harmonic and interharmonic analysis for assessing distortion and compliance with network limits</li>
<li data-start="2163" data-end="2273">Disturbance recorder capturing waveforms and RMS trends for faults, switching events and abnormal conditions</li>
<li data-start="2276" data-end="2383">Sequence of Events recording with precise time stamps to correlate protection operations and plant events</li>
<li data-start="2386" data-end="2484">Automated power quality reports to support standards-based assessment and long-term benchmarking</li>
</ul>
<h4>Communications and system integration</h4>
<ul>
<li data-start="2531" data-end="2621">Ethernet and serial interfaces for flexible connection to control and monitoring systems</li>
<li data-start="2624" data-end="2742">Support for Modbus RTU/TCP, DNP3 and IEC 60870-5-101/104 for integration into existing SCADA and RTU infrastructures</li>
<li data-start="2745" data-end="2811">IEC 61850 support for modern substation automation architectures</li>
<li data-start="2814" data-end="2918">Secure, structured data access for energy management, power quality analysis and centralised reporting</li>
</ul>
<h4>Typical applications</h4>
<ul>
<li data-start="2948" data-end="3057">Utility and industrial substations requiring revenue metering and power quality analysis in the same device</li>
<li data-start="3060" data-end="3158">Main and feeder switchboards in industrial plants, hospitals, transport and commercial buildings</li>
<li data-start="3161" data-end="3249">Monitoring of critical LV and MV feeders supplying sensitive or mission-critical loads</li>
<li data-start="3252" data-end="3379">Retrofit projects where detailed disturbance recording and Class A power quality data are required without major panel redesign</li>
</ul>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>SATEC EM235 PRO power meter</title>
		<link>https://hitec-instruments.co.uk/product/satec-em235-pro-power-meter-acdc/</link>
		
		<dc:creator><![CDATA[Marketing Hitec]]></dc:creator>
		<pubDate>Mon, 01 Dec 2025 18:33:05 +0000</pubDate>
				<guid isPermaLink="false">https://hitec-instruments.co.uk/?post_type=product&#038;p=7066</guid>

					<description><![CDATA[The SATEC EM235 DC meter is certified as compliant with CoP11 for Asset Metering Types 2 and 3. The EM235 PRO provides AC and DC power and energy metering, event and waveform recording and industrial communications. The EM235-PQ-A version adds IEC 61000-4-30 Ed. 3.1 Class A power quality analysis and EN 50160 reporting.

&#160;]]></description>
										<content:encoded><![CDATA[<h5>The SATEC EM235 PRO is a compact DIN-rail power meter for AC and DC measurement of voltage, current, power, energy and frequency. The EM235-PQ-A version provides Class A power quality analysis, waveform capture and EN 50160 reporting.</h5>
<p>Modular plug-in I/O and auxiliary power modules, dual-port Ethernet and support for IEC 61850, DNP3 and IEC 60870-5-101/104 make the EM235 PRO suitable for substation automation, industrial applications, renewable energy and commercial energy management.</p>
<p><a href="https://hitec-instruments.co.uk/wp-content/uploads/2026/08/PRO-SERIES-335-EM235-DATASHEET-V-9-15.pdf" target="_blank" rel="noopener"><span dir="auto" style="vertical-align: inherit;"><span dir="auto" style="vertical-align: inherit;"><span dir="auto" style="vertical-align: inherit;"><span dir="auto" style="vertical-align: inherit;"><span dir="auto" style="vertical-align: inherit;"><span dir="auto" style="vertical-align: inherit;">Technical specifications of the SATEC PM335 PRO and EM235 PRO</span></span></span></span></span></span></a></p>
<h5>Key Features</h5>
<ul>
<li>Class A Power Quality Analysis, Edition 3 (IEC 61000-4-30)</li>
<li>EN 50160 reports and power quality event logging – EM235-PQ-A</li>
<li>High-resolution waveform capture</li>
<li>Harmonic and interharmonic analysis</li>
<li>Programmable thresholds and event-driven recording</li>
<li>Voltage, current, power, energy and frequency measurement</li>
<li>Integrated DC current measurement using <a href="https://hitec-instruments.co.uk/product/high-accuracy-dc-current-sensors/" target="_blank" rel="noopener">SATEC U-HACS</a> or <a href="https://hitec-instruments.co.uk/product/hacs-high-accuracy-current-sensors/" target="_blank" rel="noopener">Hall-effect sensors</a></li>
</ul>
<h5>Inputs and I/O</h5>
<ul>
<li>Galvanically isolated voltage and current inputs</li>
<li>Direct DC voltage measurement: 10 –1000 V DC</li>
<li>DC voltage measurement up to 1,500 V DC via adapter</li>
<li>DC current inputs via U-HACS/Hall-effect sensors (up to 3000 A DC)</li>
<li>Optional built-in I/O: 2 DI, 1 SSR output, 1 AI</li>
<li>Modular expansion up to 24 digital inputs</li>
<li>Modular expansion up to 12 digital outputs</li>
<li>Modular expansion up to 12 analogue outputs</li>
</ul>
<h5 data-start="93" data-end="143">Data recording and event logging</h5>
<ul>
<li>Waveform recording up to 256 samples/cycle</li>
<li>Time-stamped event logging</li>
<li>Programmable data logging on periodic, internal and external triggers</li>
<li>Synchronous event capture across multiple PRO devices</li>
<li>16 GB onboard memory for long-term waveform and data recording</li>
</ul>
<h5>Communication and I/O</h5>
<ul>
<li>Dual-port Ethernet for SCADA and substation automation</li>
<li>IEC 61850 communication for digital substations</li>
<li>DNP3 and IEC 60870-5-101/104 support</li>
<li>Modbus TCP and Modbus RTU for SCADA and third-party system integration</li>
<li>USB Type-C port for local configuration and maintenance</li>
<li>Digital I/O modules and expansions for signalling, alarms and control</li>
</ul>
<h5>Applications</h5>
<ul>
<li>Energy Management</li>
<li><a href="https://hitec-instruments.co.uk/dc-metering-dc-coupled-solar-pv-bess/" target="_blank" rel="noopener">DC Metering</a></li>
<li>SCADA Integration</li>
<li>Substation Automation</li>
<li>Industrial Monitoring</li>
<li>Renewable Energy</li>
<li>Data Centres</li>
<li>Power Quality Compliance Reporting (Class A, EN50160)</li>
</ul>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>SATEC PM180 Power Quality Analyser</title>
		<link>https://hitec-instruments.co.uk/product/satec-pm180-power-quality-analyser/</link>
		
		<dc:creator><![CDATA[Marketing Hitec]]></dc:creator>
		<pubDate>Sat, 29 Nov 2025 11:07:47 +0000</pubDate>
				<guid isPermaLink="false">https://hitec-instruments.co.uk/?post_type=product&#038;p=6978</guid>

					<description><![CDATA[SATEC PM180 Power Quality Analyser is a Class A modular device for industrial, utility and commercial power quality monitoring and revenue metering.

&#160;]]></description>
										<content:encoded><![CDATA[<h5>The SATEC PM180 Power Quality Analyser is used for Class A power quality monitoring, disturbance analysis and fault analysis on MV and LV feeders</h5>
<p>It combines several functions in one modular platform – power and energy metering, power quality analysis, digital fault recording, transient recording, phasor measurement (PMU) and bay control – reducing panel space, wiring and engineering effort. Hot-swappable add-on cards allow you to tailor each device to the required mix of I/O and applications.</p>
<h5><a class="link" title="Enegry Network Association - Engineering Recommendation G99" href="https://www.energynetworks.org/assets/images/Files/ENA_EREC_G99_Issue_1_Amendment_9_(2022).pdf" target="_blank" rel="noopener">Compliance with ENA EREC G99</a></h5>
<h5>Key functions</h5>
<ul>
<li>Class A power quality analysis compliant with IEC 61000-4-30 Edition 3: voltage sags and swells, interruptions, flicker, unbalance, harmonics and interharmonics up to the 63rd order, THD and directional power quality events.</li>
<li>Revenue-grade energy metering with Class 0.2 / 0.2S accuracy per IEC 62053-22 and ANSI C12.20, including advanced Time-of-Use functionality.</li>
<li>Integrated digital fault recording and transient recording: current faults up to 40×In and transient voltage recording up to 2 kV at 1024 samples per cycle, with waveform capture and RMS trend analysis.</li>
<li>Built-in phasor measurement unit (PMU) compliant with IEEE C37.118.1, supporting synchrophasor, frequency and ROCOF measurements and IEC 61850-9-2 sampled values.</li>
</ul>
<h5>Measurement inputs and I/O</h5>
<ul>
<li>Galvanically isolated voltage and current inputs for both measurement and protection CTs, with extended ranges when fitted with fault-recorder modules.</li>
<li>Up to 48 digital inputs, up to 24 relay outputs and up to 12 analogue inputs and 12 analogue outputs using plug-in I/O cards.</li>
<li>Flexible automation, status monitoring and bay-level control for MV and LV feeders.</li>
</ul>
<h5 data-start="93" data-end="143">Digital fault recording and sequence of events</h5>
<ul>
<li>Built-in digital fault recorder with four current channels and three AC voltage channels, capturing fault currents up to 20×In (100 A at 5 A nominal).</li>
<li>Optional DFR module for separate metering and protection CTs, extending the fault-current range up to 40×In (200 A).</li>
<li>Sequence of Events (SoE) recorder with 1 ms time resolution and up to 48 digital inputs, providing a detailed chronology of plant and feeder events.</li>
<li>Fault records exportable in PQDIF and COMTRADE formats for analysis in third-party power-quality and protection tools.</li>
</ul>
<h5>Communication &amp; I/O</h5>
<ul>
<li>Communication interfaces include Ethernet and RS-485, with optional IRIG-B time synchronisation, redundant Ethernet and fibre TX-FX modules.</li>
<li>Supported protocols: Modbus RTU and TCP, DNP3, IEC 60870-5-101/104 and optional IEC 61850 Edition 2 with GOOSE messaging and report control blocks.</li>
<li>Simple integration with SCADA systems and IEC 61850 digital substation architectures.</li>
<li>The SATEC PM180 Power Quality Analyser supports these communication protocols natively, allowing seamless integration into existing SCADA and substation architectures.</li>
</ul>
<h5>Substation automation and IEC 61850</h5>
<ul>
<li>Acts as a bay controller unit (BCU) for MV and LV feeders, combining measurement, protection supervision and breaker control in a single device.</li>
<li>Native IEC 61850 Edition 2 support with GOOSE messaging and report control blocks for seamless integration into digital substation architectures.</li>
<li>Allows synchrophasor data from the SATEC PM180 Power Quality Analyser to be exchanged with a phasor data concentrator (PDC), enabling wide-area monitoring schemes.</li>
<li>The SATEC PM180 Power Quality Analyser also supports wide-area phasor-based monitoring when used with a station-level PDC, providing real-time visibility of network stability.</li>
</ul>
<h5>Typical applications</h5>
<p>The SATEC PM180 Power Quality Analyser is used for Class A power quality monitoring, disturbance and fault analysis on MV and LV feeders, synchrophasor-based monitoring in transmission networks, renewable generation PQ compliance and IEC 61850 substations.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>SATEC PM335 PRO</title>
		<link>https://hitec-instruments.co.uk/product/satec-pm335-pro/</link>
		
		<dc:creator><![CDATA[Maksym Sokolyk]]></dc:creator>
		<pubDate>Tue, 18 Nov 2025 19:25:22 +0000</pubDate>
				<guid isPermaLink="false">https://hitec-instruments.co.uk/?post_type=product&#038;p=6031</guid>

					<description><![CDATA[SATEC PM335 PRO is a cost-effective power meter specifically designed for advanced power monitoring applications involving both AC and DC currents.
Equipped with waveform recording capabilities and 16GB storage capacity, it serves as a robust Class A, Ed. 3 power-quality analyzer and event recorder.]]></description>
										<content:encoded><![CDATA[<p>PM335 PRO is a panel-mounted meter designed with a form factor that fits 4-inch round or 92×92mm square cutouts. It monitors voltage, current, power, frequency, and energy measurements, while also providing power quality analysis and data logging capabilities.</p>
<p>PM335 PRO supports multiple communication protocols, including IEC 61850, DNP3, and IEC 60870-5-101/104, along with dual-port Ethernet connectivity. As a result, it serves as the ultimate solution for power monitoring, meeting and even exceeding the current requirements in utility, substation, industrial automation, and commercial energy management applications.</p>
<h5>Power Quality</h5>
<ul>
<li>Class A, Ed. 3.1 analyser per IEC 61000-4-30</li>
<li>EN50160 reports</li>
<li>Waveform capture and recording up to 256 samples/cycle</li>
<li>Up to 0.0001 Hz resolution</li>
<li>Leakage current detection via 4th current input</li>
<li>Individual harmonics, up to the 63rd harmonic</li>
<li><a class="link" title="Energy Network Association - Engineering Recommendation G99" href="https://www.energynetworks.org/assets/images/Files/ENA_EREC_G99_Issue_1_Amendment_9_(2022).pdf" target="_blank" rel="noopener">Compliance with ENA EREC G99</a></li>
</ul>
<p><a style="color: #272d4e; text-decoration: underline;" href="https://hitec-instruments.co.uk/dc-metering-dc-coupled-solar-pv-bess/" target="_blank" rel="noopener">DC metering</a> with <a style="color: #272d4e; text-decoration: underline;" href="https://hitec-instruments.co.uk/product/high-accuracy-dc-current-sensors/" target="_blank" rel="noopener">UHACS</a> or <a style="color: #272d4e; text-decoration: underline;" href="https://hitec-instruments.co.uk/product/hacs-high-accuracy-current-sensors/" target="_blank" rel="noopener">Hall Effect Sensors</a></p>
<ul>
<li>Up to 4000A DC with SATEC supplied sensors</li>
<li>Up to 820V DC direct measurement</li>
<li>Up to 1500V DC with supplied <a style="color: #272d4e; text-decoration: underline;" href="https://hitec-instruments.co.uk/product/voltage-ratio-module-dc-metering/" target="_blank" rel="noopener">Voltage Ratio Module</a></li>
</ul>
<h5>Revenue Meter</h5>
<ul>
<li>Class 0.2/0.2S accuracy; anti-tamper design; IR interface</li>
</ul>
<h5>Communication &amp; I/O</h5>
<ul>
<li>Dual Port Ethernet: RSTP support</li>
<li>IEC 61850</li>
<li>Open protocol: Modbus TCP/RTU, DNP3, IEC 60870-5-101/104</li>
<li>USB port (Type C)</li>
<li>Built-in I/O (optional): 1 RO; 2 DI; 1 AI</li>
<li>Modular I/O: up to 24 digital I/O</li>
</ul>
]]></content:encoded>
					
		
		